c/kWh
Energy rating (cooling)
2.5
Heating: 0
Annual electricity use
18,705 kWh
4,339 cooling + 14,366 heating
Estimated running cost
$5,986 / year
$499 / month Β· $59,856 over 10 years
Capacity
45 kW cooling
50 kW heating

36% more electricity than the median of 42 comparable 50 kW reverse cycle multi-split / vrf registrations (13,803 kWh a year) in the mixed zone. Uses less than 26% of them.

Across all 3,680 air conditioner registrations sold in Australia, it uses less than 3% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Mitsubishi Electric PUHY-EP400YNW-A1-BS running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 40,907$13,090$130,902
Mixed zone 18,705$5,986$59,856
Hot zone 13,726$4,392$43,923

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 45 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
Toshiba MMY-MUP14S1HT8P-A40 kW heating40 kW cooling3,918 kWh/yr2.5$1,254
Panasonic U-16MF3R750 kW heating45 kW cooling4,064 kWh/yr2.5$1,300
Toshiba MMY-MUP16S1HT8P-A50 kW heating45 kW cooling4,443 kWh/yr2.5$1,422
Mitsubishi Electric PUHY-M350YXM-A40 kW heating40 kW cooling5,003 kWh/yr1.5$1,601
Mitsubishi Electric PUHY-M350YXM series40 kW heating40 kW cooling5,003 kWh/yr1.5$1,601

Air conditioners similar to the Mitsubishi Electric PUHY-EP400YNW-A1-BS

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Daikin REYA16AYM50 kW heating45 kW cooling11,471 kWh/yr3$3,671
Toshiba MMY-MUP16S1HT8P-A50 kW heating45 kW cooling4,443 kWh/yr2.5$1,422
Hitachi RAS-160RNCCLW50 kW heating45 kW cooling11,174 kWh/yr2.5$3,576
Mitsubishi Heavy Industries FDC450KXZRE245 kW heating45 kW cooling11,109 kWh/yr2$3,555
Daikin REYQ16TAY150 kW heating45 kW cooling14,331 kWh/yr2$4,586
Panasonic U-16MF3R750 kW heating45 kW cooling4,064 kWh/yr2.5$1,300
Mitsubishi Heavy Industries FDC450KXZE250 kW heating45 kW cooling11,292 kWh/yr2.5$3,613
Hitachi RAS-160RNCBLW47.5 kW heating45 kW cooling11,647 kWh/yr2$3,727

Compare PUHY-EP400YNW-A1-BS with another model

Mitsubishi Electric PUHY-EP400YNW-A1-BS specifications

Type
Reverse cycle
Configuration
Multi-split / VRF
Air distribution
Ducted or non-ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
45.00 kW
Cooling power input
12.11 kW
Rated heating capacity (7 Β°C)
50.00 kW
Heating power input
12.23 kW
EER, full load (tested)
3.72
COP, full load (tested)
4.27
Rated AEER
3.63
Rated ACOP
4.00
Standby power (PIA)
78.6 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Thailand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Mitsubishi Electric PUHY-EP400YNW-A1-BS zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––5,61710,138
Coldresidential2.50.02,83538,072
Mixedcommercial––7,2444,931
Mixedresidential2.50.04,33914,366
Hotcommercial––16,148856
Hotresidential3.01.512,3231,403
Part-load test points (18 values)
h__h2_ext_cap_power_rated
10140 W
c__t1_half_cap_power_rated
5100 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
5220 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
20600 W
h__h1_half_cap_heat_cap_rated
25000 W
h__h2_is_capable_extended_load
Yes
c__low_temp_half_cap_power_rated
4160 W
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
22500 W
c__low_temp_have_half_cap_results
Yes
c__low_temp_half_cap_cooling_cap_rated
22500 W

Other model numbers on registration AAC9251

Registered together and sharing the same test results. Usually variants of the same unit.

Australian GEMS registration details

Registration number
AAC9251
GEMS registration id
171954
Status
approved, available (self-reported)
Registration expires
20 August 2030
Registered for sale in
Australia, New Zealand
Family
PUHY-EP400YNW-A1 Series
Regulatory standard
[SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.4:2012
MEPS
2019
Product class
Class 21

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: MitsubishiElectric.com.au. How the derived figures are calculated.