c/kWh
Energy rating (cooling)
2.5
Heating: 0
Annual electricity use
18,705 kWh
4,339 cooling + 14,366 heating
Estimated running cost
$5,986 / year
$499 / month Β· $59,856 over 10 years
Capacity
45 kW cooling
50 kW heating

37% more electricity than the median of 41 comparable 50 kW reverse cycle registrations (13,613 kWh a year) in the mixed zone. Uses less than 27% of them.

Across all 3,638 air conditioner registrations sold in Australia, it uses less than 3% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Mitsubishi Electric PUHY-EP400YNW-A1 running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 40,907$13,090$130,902
Mixed zone 18,705$5,986$59,856
Hot zone 13,726$4,392$43,923

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 45 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
Toshiba MMY-MUP14S1HT8P-A40 kW heating40 kW cooling3,918 kWh/yr2.5$1,254
Panasonic U-16MF3R750 kW heating45 kW cooling4,064 kWh/yr2.5$1,300
Toshiba MMY-MUP16S1HT8P-A50 kW heating45 kW cooling4,443 kWh/yr2.5$1,422
Mitsubishi Electric PUHY-M350YXM-A40 kW heating40 kW cooling5,003 kWh/yr1.5$1,601
Mitsubishi Electric PUHY-M350YXM-A-BS40 kW heating40 kW cooling5,003 kWh/yr1.5$1,601

Air conditioners similar to the Mitsubishi Electric PUHY-EP400YNW-A1

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Daikin REYA16AYM50 kW heating45 kW cooling11,471 kWh/yr3$3,671
Toshiba MMY-MUP16S1HT8P-A50 kW heating45 kW cooling4,443 kWh/yr2.5$1,422
Mitsubishi Heavy Industries FDC450KXZE250 kW heating45 kW cooling11,292 kWh/yr2.5$3,613
Mitsubishi Heavy Industries FDC450KXZRE245 kW heating45 kW cooling11,109 kWh/yr2$3,555
Daikin REYQ16TAY150 kW heating45 kW cooling14,331 kWh/yr2$4,586
Panasonic U-16MF3R750 kW heating45 kW cooling4,064 kWh/yr2.5$1,300
Hitachi RAS-160RNCCLW50 kW heating45 kW cooling11,174 kWh/yr2.5$3,576
Hitachi RAS-160RNCBLW47.5 kW heating45 kW cooling11,647 kWh/yr2$3,727

Compare PUHY-EP400YNW-A1 with another model

Mitsubishi Electric PUHY-EP400YNW-A1 specifications

Type
Reverse cycle
Configuration
–
Air distribution
Ducted or non-ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
45.00 kW
Cooling power input
–
Rated heating capacity (7 Β°C)
50.00 kW
Heating power input
–
EER, full load (tested)
3.72
COP, full load (tested)
4.27
Rated AEER
3.63
Rated ACOP
4.00
Standby power (PIA)
78.6 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Thailand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Mitsubishi Electric PUHY-EP400YNW-A1 zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––5,61710,138
Coldresidential2.50.02,83538,072
Mixedcommercial––7,2444,931
Mixedresidential2.50.04,33914,366
Hotcommercial––16,148856
Hotresidential3.01.512,3231,403
Part-load test points (18 values)
h__h2_ext_cap_power_rated
10140 W
c__t1_half_cap_power_rated
5100 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
5220 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
20600 W
h__h1_half_cap_heat_cap_rated
25000 W
h__h2_is_capable_extended_load
Yes
c__low_temp_half_cap_power_rated
4160 W
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
22500 W
c__low_temp_have_half_cap_results
Yes
c__low_temp_half_cap_cooling_cap_rated
22500 W

Other model numbers on registration AAC9251

Registered together and sharing the same test results. Usually variants of the same unit.

Australian GEMS registration details

Registration number
AAC9251
GEMS registration id
–
Status
approved
Registration expires
20 August 2030
Registered for sale in
Australia, New Zealand
Family
PUHY-EP400YNW-A1 Series
Regulatory standard
Greenhouse and Energy Minimum Standards (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.4:2012
MEPS
2019
Product class
21

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 28 October 2026; last checked 29 October 2026. Manufacturer: MitsubishiElectric.com.au. How the derived figures are calculated.