c/kWh
Energy rating (cooling)
2.5
Heating: 0
Annual electricity use
17,446 kWh
3,857 cooling + 13,589 heating
Estimated running cost
$5,583 / year
$465 / month Β· $55,827 over 10 years
Capacity
40 kW cooling
45 kW heating

65% more electricity than the median of 18 comparable 40 kW reverse cycle registrations (10,587 kWh a year) in the mixed zone. Uses less than 11% of them.

Across all 3,638 air conditioner registrations sold in Australia, it uses less than 3% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Mitsubishi Electric PUHY-P350YNW-A1-BS running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 38,458$12,307$123,066
Mixed zone 17,446$5,583$55,827
Hot zone 12,201$3,904$39,043

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 40 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
Toshiba MMY-MUP14S1HT8P-A40 kW heating40 kW cooling3,918 kWh/yr2.5$1,254
Mitsubishi Electric PUHY-M350YXM-A-BS40 kW heating40 kW cooling5,003 kWh/yr1.5$1,601
Mitsubishi Electric PUHY-M350YXM-A40 kW heating40 kW cooling5,003 kWh/yr1.5$1,601
Panasonic U-14MF3R745 kW heating40 kW cooling8,732 kWh/yr3$2,794
Mitsubishi Heavy Industries FDC400KXZE245 kW heating40 kW cooling9,498 kWh/yr2.5$3,039

Air conditioners similar to the Mitsubishi Electric PUHY-P350YNW-A1-BS

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Panasonic U-14MF3R745 kW heating40 kW cooling8,732 kWh/yr3$2,794
Toshiba MMY-MUP1401FT8P-A40 kW heating40 kW cooling10,278 kWh/yr3.5$3,289
Hitachi RAS-140RNCBLW45 kW heating40 kW cooling10,547 kWh/yr2$3,375
Daikin REYA14AYM45 kW heating40 kW cooling10,627 kWh/yr2.5$3,401
Mitsubishi Heavy Industries FDC400KXZE245 kW heating40 kW cooling9,498 kWh/yr2.5$3,039
Mitsubishi Heavy Industries FDC400KXZRE240 kW heating40 kW cooling10,236 kWh/yr2.5$3,276
Hitachi RAS-140HNCELW45 kW heating40 kW cooling9,658 kWh/yr2.5$3,091
Toshiba MMY-MUP14S1HT8P-A40 kW heating40 kW cooling3,918 kWh/yr2.5$1,254

Compare PUHY-P350YNW-A1-BS with another model

Mitsubishi Electric PUHY-P350YNW-A1-BS specifications

Type
Reverse cycle
Configuration
–
Air distribution
Ducted or non-ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
40.00 kW
Cooling power input
–
Rated heating capacity (7 Β°C)
45.00 kW
Heating power input
–
EER, full load (tested)
3.57
COP, full load (tested)
4.28
Rated AEER
3.49
Rated ACOP
4.02
Standby power (PIA)
76.0 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Thailand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Mitsubishi Electric PUHY-P350YNW-A1-BS zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––4,7429,510
Coldresidential2.50.02,50835,950
Mixedcommercial––6,2284,633
Mixedresidential2.50.03,85713,589
Hotcommercial––14,050801
Hotresidential3.01.510,8901,311
Part-load test points (18 values)
h__h2_ext_cap_power_rated
9870 W
c__t1_half_cap_power_rated
4520 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
4770 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
17800 W
h__h1_half_cap_heat_cap_rated
22500 W
h__h2_is_capable_extended_load
Yes
c__low_temp_half_cap_power_rated
3590 W
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
20000 W
c__low_temp_have_half_cap_results
Yes
c__low_temp_half_cap_cooling_cap_rated
20000 W

Other model numbers on registration AAC9262

Registered together and sharing the same test results. Usually variants of the same unit.

Australian GEMS registration details

Registration number
AAC9262
GEMS registration id
–
Status
approved
Registration expires
20 August 2030
Registered for sale in
Australia, New Zealand
Family
PUHY-P350YNW-A1 Series
Regulatory standard
Greenhouse and Energy Minimum Standards (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.4:2012
MEPS
2019
Product class
21

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 28 October 2026; last checked 29 October 2026. Manufacturer: MitsubishiElectric.com.au. How the derived figures are calculated.