c/kWh
Energy rating (cooling)
2
Heating: 0
Annual electricity use
3,057 kWh
Estimated running cost
$1,009 / year
$84 / month Β· $10,088 over 10 years
Capacity
43 kW cooling
40.3 kW heating

19% less electricity than the median of 13 comparable 40 kW reverse cycle ducted packaged registrations (3,797 kWh a year) in the cold zone. Uses less than 85% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 61% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

APAC P040AHR3SA-LBB running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 3,057$1,009$10,088
Mixed zone 4,628$1,527$15,272
Hot zone 13,035$4,302$43,016

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps similar to the APAC P040AHR3SA-LBB

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Daikin UAYQ150CY1A43.1 kW heating42.8 kW cooling24,646 kWh/yr1.5$8,133
AIRSTAGE RAQ/K/WP/11843.6 kW heating43.3 kW cooling25,680 kWh/yr1$8,474
AIRSTAGE RAQ/K/WP/ECO/11843.6 kW heating43.3 kW cooling25,680 kWh/yr1$8,474
Temperzone OPA450RLTFPQ44.4 kW heating43.3 kW cooling24,476 kWh/yr2$8,077
Temperzone OPA465RKTB41.3 kW heating42.5 kW cooling4,036 kWh/yr1$1,332
Daikin UAYN400AFY1A37.6 kW heating40.8 kW cooling31,483 kWh/yr1.5$10,389

Other APAC models of similar capacity

ModelStarsEst. cost / yrCompare
APAC P040AVR3SA-40.3 kW heating43 kW cooling3,057 kWh/yr2$1,009
APAC P040AVR3SA-LTS40.3 kW heating43 kW cooling3,057 kWh/yr2$1,009

Compare P040AHR3SA-LBB with another model

APAC P040AHR3SA-LBB specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
43.00 kW
Cooling power input
11.30 kW
Rated heating capacity (7 Β°C)
40.30 kW
Heating power input
10.50 kW
EER, full load (tested)
3.62
COP, full load (tested)
3.67
Rated AEER
3.69
Rated ACOP
3.72
Standby power (PIA)
100.0 W
Compressor
Variable speed
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Australia, Malaysia

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

APAC P040AHR3SA-LBB zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––6,990–
Coldresidential2.00.03,057–
Mixedcommercial––8,498–
Mixedresidential2.00.04,628–
Hotcommercial––17,885–
Hotresidential2.50.013,035–
Part-load test points (8 values)
c__t1_min_cap_power_rated
6170 W
c__t1_have_min_cap_results
Yes
c__low_temp_min_cap_power_rated
5710 W
c__t1_min_cap_cooling_cap_rated
27380 W
c__low_temp_full_cap_power_rated
10280 W
c__low_temp_have_full_cap_results
Yes
c__low_temp_min_cap_cooling_cap_rated
28700 W
c__low_temp_full_cap_cooling_cap_rated
45730 W

Other model numbers on registration AAC7444

Registered together and sharing the same test results. Usually variants of the same unit.

New Zealand E3 registration details

Registration number
AAC7444
GEMS registration id
153711
Status
approved, available (self-reported)
Registration expires
24 April 2028
Registered for sale in
Australia, Fiji, New Zealand
Family
P040AHR3SA-
Regulatory standard
[SEER Non Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
Simulation
MEPS
2019
Product class
Class 7

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. Manufacturer: rinnai.com.au. How the derived figures are calculated.