New Zealand Β· costs in NZD

Reverse cycle packaged air conditioner
Daikin UAYQ150CY1A Heat Pump
Daikin UAYQ150CY1A is a 42.8 kW reverse cycle ducted packaged heat pump registered for sale in New Zealand under the trans-Tasman E3 energy rating scheme (registration AAC7778).
- Energy rating (cooling)
- 1.5
- Heating: 1
- Annual electricity use
- 24,646 kWh
- 3,883 cooling + 20,763 heating
- Estimated running cost
- $8,133 / year
- $678 / month Β· $81,332 over 10 years
- Capacity
- 42.8 kW cooling
- 43.1 kW heating
549% more electricity than the median of 13 comparable 40 kW reverse cycle ducted packaged registrations (3,797 kWh a year) in the cold zone. Uses less than 23% of them.
Across all 3,611 air conditioner registrations sold in Australia, it uses less than 5% (this compares very different sizes, so the cohort figure above is the useful one).
Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ 33c/kWh in NZD; change the price above to your tariff.
Daikin UAYQ150CY1A running cost by climate zone
| Climate zone | kWh / year | Per year | 10 years |
|---|---|---|---|
| Cold zone | 24,646 | $8,133 | $81,332 |
| Mixed zone | 14,090 | $4,650 | $46,497 |
| Hot zone | 18,518 | $6,111 | $61,109 |
At 33c/kWh. Formula: cost = annual kWh Γ price. The kWh figure is the labelβs residential estimate for that zone; commercial-profile figures are in the specifications.
Heat pumps that use less electricity
Same configuration and type, cooling capacity within 12% of 42.8 kW, at least 3% lower annual kWh in the cold zone.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| APAC P040AHR3SA-LTT40.3 kW heating43 kW cooling3,057 kWh/yr | 2 | $1,009 | |
| APAC P040AHR3SA-RTT40.3 kW heating43 kW cooling3,057 kWh/yr | 2 | $1,009 | |
| Actron Air PCG400R39.5 kW heating39.2 kW cooling3,697 kWh/yr | 1 | $1,220 | |
| Actron Air PCG400L39.5 kW heating39.2 kW cooling3,697 kWh/yr | 1 | $1,220 | |
| Caa VPA045R3AC49.4 kW heating46.1 kW cooling3,718 kWh/yr | 1.5 | $1,227 |
Heat pumps similar to the Daikin UAYQ150CY1A
Technically comparable registrations: same configuration and type, capacity within 12%.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| APAC P040AVR3SA-RTS40.3 kW heating43 kW cooling3,057 kWh/yr | 2 | $1,009 | |
| APAC P040AHR3SA-RTR40.3 kW heating43 kW cooling3,057 kWh/yr | 2 | $1,009 | |
| Temperzone OPA465RKTB41.3 kW heating42.5 kW cooling4,036 kWh/yr | 1 | $1,332 | |
| AIRSTAGE RAQ/K/WP/* 11843.6 kW heating43.3 kW cooling25,680 kWh/yr | 1 | $8,474 | |
| AIRSTAGE RAQ/K/WP/ECO/11843.6 kW heating43.3 kW cooling25,680 kWh/yr | 1 | $8,474 | |
| Temperzone OPA450RLTFPQ44.4 kW heating43.3 kW cooling24,476 kWh/yr | 2 | $8,077 | |
| Caa VPA045R3AC49.4 kW heating46.1 kW cooling3,718 kWh/yr | 1.5 | $1,227 |
Other Daikin models of similar capacity
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Daikin UAYN400AFY1A37.6 kW heating40.8 kW cooling31,483 kWh/yr | 1.5 | $10,389 |
Compare UAYQ150CY1A with another model
Daikin UAYQ150CY1A specifications
- Type
- Reverse cycle
- Configuration
- Packaged
- Air distribution
- Ducted
- Indoor unit
- β
- Rated cooling capacity (35 Β°C)
- 42.81 kW
- Cooling power input
- 13.64 kW
- Rated heating capacity (7 Β°C)
- 43.10 kW
- Heating power input
- 12.86 kW
- EER, full load (tested)
- 3.00
- COP, full load (tested)
- 3.39
- Rated AEER
- 3.10
- Rated ACOP
- 3.31
- Standby power (PIA)
- 46.6 W
- Compressor
- Fixed speed
- Refrigerant
- R410A
- Power supply
- Three phase
- Indoor sound power
- β
- Outdoor sound power
- β
- Demand response (AS/NZS 4755)
- No
- Dimensions (WΓHΓD)
- 1638 Γ 1150 Γ 2063 mm
- Country of manufacture
- Malaysia
Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.
Daikin UAYQ150CY1A zoned energy rating figures
As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.
| Zone | Profile | Cooling stars | Heating stars | Cooling kWh | Heating kWh |
|---|---|---|---|---|---|
| Coldcommercial | commercial | β | β | 8,943 | 7,061 |
| Coldresidential | residential | 1.5 | 1.0 | 3,883 | 20,763 |
| Mixedcommercial | commercial | β | β | 10,975 | 3,856 |
| Mixedresidential | residential | 1.5 | 1.0 | 5,845 | 8,245 |
| Hotcommercial | commercial | β | β | 23,604 | 882 |
| Hotresidential | residential | 1.5 | 1.0 | 17,137 | 1,381 |
Part-load test points (6 values)
- h__h2_full_cap_power_rated
- 11111 W
- h__h3_have_full_cap_results
- No
- h__h2_full_cap_heat_cap_rated
- 34583 W
- c__low_temp_full_cap_power_rated
- 12636 W
- c__low_temp_have_full_cap_results
- Yes
- c__low_temp_full_cap_cooling_cap_rated
- 46477 W
New Zealand E3 registration details
- Registration number
- AAC7778
- GEMS registration id
- 156597
- Status
- approved, available (self-reported)
- Registration expires
- 13 September 2028
- Registered for sale in
- Australia, New Zealand
- Family
- β
- Regulatory standard
- [SEER Non Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
- Test standard
- AS/NZS 3823.1.2:2012
- MEPS
- 2019
- Product class
- Class 7
Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: daikin.com.au. How the derived figures are calculated.