New Zealand Β· costs in NZD

Reverse cycle packaged air conditioner
Daikin UAXYA130SY1 Heat Pump
Daikin UAXYA130SY1 is a 130 kW reverse cycle ducted packaged heat pump registered for sale in New Zealand under the trans-Tasman E3 energy rating scheme (registration AAC8467).
- Energy rating (cooling)
- 1
- Heating: 0
- Annual electricity use
- 12,660 kWh
- Estimated running cost
- $4,178 / year
- $348 / month Β· $41,778 over 10 years
- Capacity
- 130 kW cooling
- 130 kW heating
69% less electricity than the median of 53 comparable 80 kW and above reverse cycle ducted packaged registrations (41,538 kWh a year) in the cold zone. Uses less than 74% of them.
Across all 3,611 air conditioner registrations sold in Australia, it uses less than 11% (this compares very different sizes, so the cohort figure above is the useful one).
Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ 33c/kWh in NZD; change the price above to your tariff.
Daikin UAXYA130SY1 running cost by climate zone
| Climate zone | kWh / year | Per year | 10 years |
|---|---|---|---|
| Cold zone | 12,660 | $4,178 | $41,778 |
| Mixed zone | 18,763 | $6,192 | $61,918 |
| Hot zone | 52,555 | $17,343 | $173,432 |
At 33c/kWh. Formula: cost = annual kWh Γ price. The kWh figure is the labelβs residential estimate for that zone; commercial-profile figures are in the specifications.
Heat pumps that use less electricity
Same configuration and type, cooling capacity within 12% of 130 kW, at least 3% lower annual kWh in the cold zone.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Temperzone OPA1400RKTMDF-P115.1 kW heating127.6 kW cooling9,419 kWh/yr | 2 | $3,108 | |
| APAC P115AHR3SA-CTR109 kW heating115.3 kW cooling10,211 kWh/yr | 1 | $3,370 | |
| APAC P115AHR3SA-109 kW heating115.3 kW cooling10,211 kWh/yr | 1 | $3,370 | |
| Caa HPC125R3AD138.3 kW heating127.5 kW cooling11,262 kWh/yr | 1.5 | $3,716 | |
| Temperzone OPA1370RKTMG-P125.5 kW heating131.6 kW cooling11,398 kWh/yr | 1.5 | $3,761 |
Heat pumps similar to the Daikin UAXYA130SY1
Technically comparable registrations: same configuration and type, capacity within 12%.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Temperzone OPA1370RKTMG-P125.5 kW heating131.6 kW cooling11,398 kWh/yr | 1.5 | $3,761 | |
| Temperzone OPA1400RKTMDF-P115.1 kW heating127.6 kW cooling9,419 kWh/yr | 2 | $3,108 | |
| Caa HPC125R3AD138.3 kW heating127.5 kW cooling11,262 kWh/yr | 1.5 | $3,716 | |
| AIRSTAGE URT-EC-WP-MS-111-SK136 kW heating127 kW cooling70,494 kWh/yr | 1.5 | $23,263 | |
| AIRSTAGE URT/EC/WP/MS/111/SK136 kW heating127 kW cooling70,494 kWh/yr | 1.5 | $23,263 | |
| Actron Air PKV1400T134 kW heating135 kW cooling12,716 kWh/yr | 1 | $4,196 | |
| APAC P115AHR3SA-CBR109 kW heating115.3 kW cooling10,211 kWh/yr | 1 | $3,370 | |
| APAC P115AHR3SA-CRR109 kW heating115.3 kW cooling10,211 kWh/yr | 1 | $3,370 |
Compare UAXYA130SY1 with another model
Daikin UAXYA130SY1 specifications
- Type
- Reverse cycle
- Configuration
- Packaged
- Air distribution
- Ducted
- Indoor unit
- β
- Rated cooling capacity (35 Β°C)
- 130.00 kW
- Cooling power input
- 41.20 kW
- Rated heating capacity (7 Β°C)
- 130.00 kW
- Heating power input
- 41.20 kW
- EER, full load (tested)
- 3.02
- COP, full load (tested)
- 3.12
- Rated AEER
- 3.05
- Rated ACOP
- 3.05
- Standby power (PIA)
- 440.0 W
- Compressor
- Variable speed, Inverter
- Refrigerant
- R32
- Power supply
- Three phase
- Indoor sound power
- β
- Outdoor sound power
- β
- Demand response (AS/NZS 4755)
- No
- Country of manufacture
- Australia
Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.
Daikin UAXYA130SY1 zoned energy rating figures
As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.
| Zone | Profile | Cooling stars | Heating stars | Cooling kWh | Heating kWh |
|---|---|---|---|---|---|
| Coldcommercial | commercial | β | β | 27,569 | β |
| Coldresidential | residential | 1.0 | 0.0 | 12,660 | β |
| Mixedcommercial | commercial | β | β | 33,738 | β |
| Mixedresidential | residential | 1.0 | 0.0 | 18,763 | β |
| Hotcommercial | commercial | β | β | 71,577 | β |
| Hotresidential | residential | 1.5 | 0.0 | 52,555 | β |
Part-load test points (1 values)
- c__low_temp_have_full_cap_results
- No
Other model numbers on registration AAC8467
Registered together and sharing the same test results. Usually variants of the same unit.
New Zealand E3 registration details
- Registration number
- AAC8467
- GEMS registration id
- 164459
- Status
- approved, available (self-reported)
- Registration expires
- 29 September 2029
- Registered for sale in
- Australia, New Zealand
- Family
- UAXYA130NY1
- Regulatory standard
- [SEER Non Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
- Test standard
- Simulation
- MEPS
- 2020
- Product class
- Class 24
Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: daikin.com.au. How the derived figures are calculated.