c/kWh
Energy rating (cooling)
1.5
Heating: 0
Annual electricity use
11,398 kWh
Estimated running cost
$3,761 / year
$313 / month Β· $37,613 over 10 years
Capacity
131.6 kW cooling
125.5 kW heating

73% less electricity than the median of 53 comparable 80 kW and above reverse cycle ducted packaged registrations (41,538 kWh a year) in the cold zone. Uses less than 77% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 12% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Temperzone OPA1370RKTMG-P running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 11,398$3,761$37,613
Mixed zone 17,279$5,702$57,021
Hot zone 51,379$16,955$169,551

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 131.6 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
Temperzone OPA1400RKTMDF-P115.1 kW heating127.6 kW cooling9,419 kWh/yr2$3,108

Heat pumps similar to the Temperzone OPA1370RKTMG-P

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Daikin UAXYA130SY1130 kW heating130 kW cooling12,660 kWh/yr1$4,178
Daikin UAXYA130NY1130 kW heating130 kW cooling12,660 kWh/yr1$4,178
Actron Air PKV1400T134 kW heating135 kW cooling12,716 kWh/yr1$4,196
Caa HPC125R3AD138.3 kW heating127.5 kW cooling11,262 kWh/yr1.5$3,716
AIRSTAGE URT-EC-WP-MS-111-SK136 kW heating127 kW cooling70,494 kWh/yr1.5$23,263
AIRSTAGE URT.EC.WP.MS 111 S.K136 kW heating127 kW cooling70,494 kWh/yr1.5$23,263

Other Temperzone models of similar capacity

ModelStarsEst. cost / yrCompare
Temperzone OPA1400RKTMDF-P115.1 kW heating127.6 kW cooling9,419 kWh/yr2$3,108
Temperzone OPA1370RLTMFQ-P130.9 kW heating136.7 kW cooling12,152 kWh/yr1.5$4,010

Compare OPA1370RKTMG-P with another model

Temperzone OPA1370RKTMG-P specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
131.60 kW
Cooling power input
41.46 kW
Rated heating capacity (7 Β°C)
125.48 kW
Heating power input
33.54 kW
EER, full load (tested)
3.17
COP, full load (tested)
3.74
Rated AEER
3.16
Rated ACOP
3.73
Standby power (PIA)
40.0 W
Compressor
Variable speed, Digital Scroll
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Australia, New Zealand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Temperzone OPA1370RKTMG-P zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––26,491–
Coldresidential1.50.011,398–
Mixedcommercial––32,695–
Mixedresidential1.50.017,279–
Hotcommercial––70,800–
Hotresidential1.50.051,379–
Part-load test points (1 values)
c__low_temp_have_full_cap_results
No

New Zealand E3 registration details

Registration number
AAC7153
GEMS registration id
150372
Status
approved, available (self-reported)
Registration expires
14 November 2027
Registered for sale in
Australia, Fiji, New Zealand
Family
–
Regulatory standard
[SEER Non Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
Test standard
Simulation
MEPS
2020
Product class
Class 24