Temperzone OPA1400RKTMDF-P is a 127.6 kW reverse cycle ducted packaged heat pump registered for sale in New Zealand under the trans-Tasman E3 energy rating scheme (registration AAC7074).
- Energy rating (cooling)
- 2
- Heating: 0
- Annual electricity use
- 9,419 kWh
- Estimated running cost
- $3,108 / year
- $259 / month Β· $31,083 over 10 years
- Capacity
- 127.6 kW cooling
- 115.1 kW heating
77% less electricity than the median of 53 comparable 80 kW and above reverse cycle ducted packaged registrations (41,538 kWh a year) in the cold zone. Uses less than 85% of them.
Across all 3,611 air conditioner registrations sold in Australia, it uses less than 15% (this compares very different sizes, so the cohort figure above is the useful one).
Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ 33c/kWh in NZD; change the price above to your tariff.
Temperzone OPA1400RKTMDF-P running cost by climate zone
| Climate zone | kWh / year | Per year | 10 years |
|---|---|---|---|
| Cold zone | 9,419 | $3,108 | $31,083 |
| Mixed zone | 14,601 | $4,818 | $48,183 |
| Hot zone | 43,444 | $14,337 | $143,365 |
At 33c/kWh. Formula: cost = annual kWh Γ price. The kWh figure is the labelβs residential estimate for that zone; commercial-profile figures are in the specifications.
Heat pumps similar to the Temperzone OPA1400RKTMDF-P
Technically comparable registrations: same configuration and type, capacity within 12%.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Caa HPC125R3AD138.3 kW heating127.5 kW cooling11,262 kWh/yr | 1.5 | $3,716 | |
| AIRSTAGE URT/EC/WP/MS/111/SK136 kW heating127 kW cooling70,494 kWh/yr | 1.5 | $23,263 | |
| AIRSTAGE URT.EC.WP.MS 111 S.K136 kW heating127 kW cooling70,494 kWh/yr | 1.5 | $23,263 | |
| Daikin UAXYA130NY1130 kW heating130 kW cooling12,660 kWh/yr | 1 | $4,178 | |
| Daikin UAXYA130RY1130 kW heating130 kW cooling12,660 kWh/yr | 1 | $4,178 | |
| Actron Air PKV1400T134 kW heating135 kW cooling12,716 kWh/yr | 1 | $4,196 |
Other Temperzone models of similar capacity
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Temperzone OPA1370RKTMG-P125.5 kW heating131.6 kW cooling11,398 kWh/yr | 1.5 | $3,761 | |
| Temperzone OPA1370RLTMFQ-P130.9 kW heating136.7 kW cooling12,152 kWh/yr | 1.5 | $4,010 |
Compare OPA1400RKTMDF-P with another model
Temperzone OPA1400RKTMDF-P specifications
- Type
- Reverse cycle
- Configuration
- Packaged
- Air distribution
- Ducted
- Indoor unit
- β
- Rated cooling capacity (35 Β°C)
- 127.56 kW
- Cooling power input
- 40.44 kW
- Rated heating capacity (7 Β°C)
- 115.08 kW
- Heating power input
- 34.60 kW
- EER, full load (tested)
- 3.15
- COP, full load (tested)
- 3.33
- Rated AEER
- 3.14
- Rated ACOP
- 3.31
- Standby power (PIA)
- 53.0 W
- Compressor
- Variable speed, Inverter
- Refrigerant
- R410A
- Power supply
- Three phase
- Indoor sound power
- β
- Outdoor sound power
- β
- Demand response (AS/NZS 4755)
- No
- Country of manufacture
- Australia, New Zealand
Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.
Temperzone OPA1400RKTMDF-P zoned energy rating figures
As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.
| Zone | Profile | Cooling stars | Heating stars | Cooling kWh | Heating kWh |
|---|---|---|---|---|---|
| Coldcommercial | commercial | β | β | 22,348 | β |
| Coldresidential | residential | 2.0 | 0.0 | 9,419 | β |
| Mixedcommercial | commercial | β | β | 27,453 | β |
| Mixedresidential | residential | 2.0 | 0.0 | 14,601 | β |
| Hotcommercial | commercial | β | β | 60,029 | β |
| Hotresidential | residential | 2.0 | 0.0 | 43,444 | β |
Part-load test points (7 values)
- c__t1_half_cap_power_rated
- 17560 W
- c__t1_have_min_cap_results
- No
- c__low_temp_half_cap_power_rated
- 15720 W
- c__low_temp_have_min_cap_results
- No
- c__t1_half_cap_cooling_cap_rated
- 69760 W
- c__low_temp_have_half_cap_results
- Yes
- c__low_temp_half_cap_cooling_cap_rated
- 67600 W
New Zealand E3 registration details
- Registration number
- AAC7074
- GEMS registration id
- 150356
- Status
- approved, available (self-reported)
- Registration expires
- 5 October 2027
- Registered for sale in
- Australia, Fiji, New Zealand
- Family
- β
- Regulatory standard
- [SEER Non Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
- Test standard
- AS/NZS 3823.1.2:2012
- MEPS
- 2020
- Product class
- Class 24
Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. How the derived figures are calculated.