New Zealand Β· costs in NZD
Reverse cycle multi-split / vrf air conditioner
Gree GMV-400WM/C-X(A) Heat Pump
Gree GMV-400WM/C-X(A) is a 40 kW reverse cycle ducted multi-split / vrf heat pump registered for sale in New Zealand under the trans-Tasman E3 energy rating scheme (registration AAC6819).
- Energy rating (cooling)
- 2.5
- Heating: 2
- Annual electricity use
- 17,377 kWh
- 2,342 cooling + 15,035 heating
- Estimated running cost
- $5,734 / year
- $478 / month Β· $57,344 over 10 years
- Capacity
- 40 kW cooling
- 40 kW heating
7% less electricity than the median of 6 comparable 40 kW reverse cycle ducted multi-split / vrf registrations (18,672 kWh a year) in the cold zone. Uses less than 67% of them.
Across all 3,611 air conditioner registrations sold in Australia, it uses less than 8% (this compares very different sizes, so the cohort figure above is the useful one).
Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ 33c/kWh in NZD; change the price above to your tariff.
Gree GMV-400WM running cost by climate zone
| Climate zone | kWh / year | Per year | 10 years |
|---|---|---|---|
| Cold zone | 17,377 | $5,734 | $57,344 |
| Mixed zone | 9,080 | $2,996 | $29,964 |
| Hot zone | 11,046 | $3,645 | $36,452 |
At 33c/kWh. Formula: cost = annual kWh Γ price. The kWh figure is the labelβs residential estimate for that zone; commercial-profile figures are in the specifications.
Heat pumps similar to the Gree GMV-400WM
Technically comparable registrations: same configuration and type, capacity within 12%.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Braemar MCHX400D323B40 kW heating40 kW cooling17,377 kWh/yr | 2.5 | $5,734 | |
| Braemar MCRX400D323B40 kW heating40 kW cooling18,672 kWh/yr | 2 | $6,162 | |
| Panasonic U-14ME2R8E45 kW heating40 kW cooling22,669 kWh/yr | 3.5 | $7,481 | |
| Haier AV14IMAURA45 kW heating40 kW cooling25,173 kWh/yr | 1.5 | $8,307 | |
| Panasonic U-14ME2R845 kW heating40 kW cooling22,669 kWh/yr | 3.5 | $7,481 |
Other Gree models of similar capacity
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Gree GMV-VQ400WM/C-X(A)40 kW heating40 kW cooling18,672 kWh/yr | 2 | $6,162 |
Compare GMV-400WM/C-X(A) with another model
Gree GMV-400WM specifications
- Type
- Reverse cycle
- Configuration
- Multi-split / VRF
- Air distribution
- Ducted
- Indoor unit
- β
- Rated cooling capacity (35 Β°C)
- 40.00 kW
- Cooling power input
- 9.93 kW
- Rated heating capacity (7 Β°C)
- 40.00 kW
- Heating power input
- 9.60 kW
- EER, full load (tested)
- 4.03
- COP, full load (tested)
- 4.17
- Rated AEER
- 3.93
- Rated ACOP
- 4.06
- Standby power (PIA)
- 76.0 W
- Compressor
- Variable speed, Inverter
- Refrigerant
- R410A
- Power supply
- Three phase
- Indoor sound power
- β
- Outdoor sound power
- β
- Demand response (AS/NZS 4755)
- Yes
- Country of manufacture
- China
Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.
Gree GMV-400WM zoned energy rating figures
As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.
| Zone | Profile | Cooling stars | Heating stars | Cooling kWh | Heating kWh |
|---|---|---|---|---|---|
| Coldcommercial | commercial | β | β | 4,964 | 4,842 |
| Coldresidential | residential | 2.5 | 2.0 | 2,342 | 15,035 |
| Mixedcommercial | commercial | β | β | 6,190 | 2,516 |
| Mixedresidential | residential | 2.5 | 2.5 | 3,588 | 5,492 |
| Hotcommercial | commercial | β | β | 13,513 | 621 |
| Hotresidential | residential | 3.5 | 3.0 | 10,112 | 934 |
Part-load test points (20 values)
- h__h2_ext_cap_power_rated
- 15610 W
- c__t1_half_cap_power_rated
- 3880 W
- c__t1_have_min_cap_results
- No
- h__h1_half_cap_power_rated
- 4090 W
- h__h1_have_min_cap_results
- No
- h__h3_have_ext_cap_results
- No
- h__h2_have_full_cap_results
- No
- h__h2_have_half_cap_results
- No
- h__h3_have_full_cap_results
- No
- h__h3_have_half_cap_results
- No
- h__h2_ext_cap_heat_cap_rated
- 35950 W
- h__h1_half_cap_heat_cap_rated
- 20000 W
- h__h2_is_capable_extended_load
- Yes
- c__low_temp_full_cap_power_rated
- 9076.02 W
- c__low_temp_half_cap_power_rated
- 3546.32 W
- c__low_temp_have_min_cap_results
- No
- c__t1_half_cap_cooling_cap_rated
- 20000 W
- c__low_temp_have_half_cap_results
- No
- c__low_temp_full_cap_cooling_cap_rated
- 43080 W
- c__low_temp_half_cap_cooling_cap_rated
- 21540 W
New Zealand E3 registration details
- Registration number
- AAC6819
- GEMS registration id
- 148169
- Status
- approved, available (self-reported)
- Registration expires
- 12 July 2027
- Registered for sale in
- Australia, Fiji, New Zealand
- Family
- β
- Regulatory standard
- [SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
- Test standard
- AS/NZS 3823.1.4:2012
- MEPS
- 2019
- Product class
- Class 21
Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. How the derived figures are calculated.