c/kWh
Energy rating (cooling)
3.5
Heating: 1
Annual electricity use
22,669 kWh
2,054 cooling + 20,615 heating
Estimated running cost
$7,481 / year
$623 / month Β· $74,808 over 10 years
Capacity
40 kW cooling
45 kW heating

21% more electricity than the median of 6 comparable 40 kW reverse cycle ducted multi-split / vrf registrations (18,672 kWh a year) in the cold zone. Uses less than 17% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 6% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Panasonic U-14ME2R8 running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 22,669$7,481$74,808
Mixed zone 10,246$3,381$33,812
Hot zone 10,013$3,304$33,043

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 40 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
Gree GMV-400WM/C-X(A)40 kW heating40 kW cooling17,377 kWh/yr2.5$5,734
Braemar MCHX400D323B40 kW heating40 kW cooling17,377 kWh/yr2.5$5,734
Braemar MCRX400D323B40 kW heating40 kW cooling18,672 kWh/yr2$6,162
Gree GMV-VQ400WM/C-X(A)40 kW heating40 kW cooling18,672 kWh/yr2$6,162

Heat pumps similar to the Panasonic U-14ME2R8

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Gree GMV-VQ400WM/C-X(A)40 kW heating40 kW cooling18,672 kWh/yr2$6,162
Braemar MCHX400D323B40 kW heating40 kW cooling17,377 kWh/yr2.5$5,734
Braemar MCRX400D323B40 kW heating40 kW cooling18,672 kWh/yr2$6,162
Haier AV14IMAURA45 kW heating40 kW cooling25,173 kWh/yr1.5$8,307
Gree GMV-400WM/C-X(A)40 kW heating40 kW cooling17,377 kWh/yr2.5$5,734

Compare U-14ME2R8 with another model

Panasonic U-14ME2R8 specifications

Type
Reverse cycle
Configuration
Multi-split / VRF
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
40.00 kW
Cooling power input
11.60 kW
Rated heating capacity (7 Β°C)
45.00 kW
Heating power input
10.40 kW
EER, full load (tested)
3.34
COP, full load (tested)
4.20
Rated AEER
3.37
Rated ACOP
4.21
Standby power (PIA)
83.0 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
Yes (mode 1 on off, mode 2 50 percent, mode 3 75 percent)
Country of manufacture
Malaysia

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Panasonic U-14ME2R8 zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––3,3435,670
Coldresidential3.51.02,05420,615
Mixedcommercial––4,5022,578
Mixedresidential3.02.03,2197,027
Hotcommercial––11,686532
Hotresidential4.04.59,184829
Part-load test points (21 values)
c__t1_min_cap_power_rated
920 W
h__h1_min_cap_power_rated
720 W
h__h2_ext_cap_power_rated
9770 W
c__t1_half_cap_power_rated
3320 W
c__t1_have_min_cap_results
Yes
h__h1_half_cap_power_rated
3800 W
h__h1_have_min_cap_results
Yes
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h1_min_cap_heat_cap_rated
4900 W
h__h2_ext_cap_heat_cap_rated
27800 W
h__h1_half_cap_heat_cap_rated
22500 W
h__h2_is_capable_extended_load
Yes
c__low_temp_min_cap_power_rated
730 W
c__t1_min_cap_cooling_cap_rated
6400 W
c__t1_half_cap_cooling_cap_rated
20000 W
c__low_temp_have_half_cap_results
No
c__low_temp_min_cap_cooling_cap_rated
7800 W

Other model numbers on registration AAC9310

Registered together and sharing the same test results. Usually variants of the same unit.

New Zealand E3 registration details

Registration number
AAC9310
GEMS registration id
170609
Status
approved, available (self-reported)
Registration expires
5 October 2030
Registered for sale in
Australia, New Zealand
Family
U-14ME2R8
Regulatory standard
[SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.4:2012
MEPS
2019
Product class
Class 21

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. How the derived figures are calculated.