c/kWh
Energy rating (cooling)
2.5
Heating: 1.5
Annual electricity use
20,722 kWh
2,777 cooling + 17,945 heating
Estimated running cost
$6,838 / year
$570 / month Β· $68,383 over 10 years
Capacity
45 kW cooling
45 kW heating

15% less electricity than the median of 10 comparable 50 kW reverse cycle ducted multi-split / vrf registrations (24,311 kWh a year) in the cold zone. Uses less than 70% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 6% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Gree GMV-450WM running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 20,722$6,838$68,383
Mixed zone 10,705$3,533$35,327
Hot zone 13,314$4,394$43,936

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 45 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
Haier AV18IMAURA56.5 kW heating50 kW cooling3,682 kWh/yr2$1,215
Gree GMV-400WM/C-X(A)40 kW heating40 kW cooling17,377 kWh/yr2.5$5,734
Braemar MCHX400D323B40 kW heating40 kW cooling17,377 kWh/yr2.5$5,734
Gree GMV-VQ400WM/C-X(A)40 kW heating40 kW cooling18,672 kWh/yr2$6,162
Braemar MCRX400D323B40 kW heating40 kW cooling18,672 kWh/yr2$6,162

Heat pumps similar to the Gree GMV-450WM

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Haier AV16IMAURA50 kW heating45 kW cooling26,645 kWh/yr1.5$8,793
Braemar MCHX450D326B45 kW heating45 kW cooling20,722 kWh/yr2.5$6,838
Panasonic U-16ME2R850 kW heating45 kW cooling28,547 kWh/yr3$9,421
Panasonic U-16ME2R8E50 kW heating45 kW cooling28,547 kWh/yr3$9,421
Braemar MCRX450D326B45 kW heating45 kW cooling22,348 kWh/yr2$7,375
Haier AV18IMAURA56.5 kW heating50 kW cooling3,682 kWh/yr2$1,215

Other Gree models of similar capacity

ModelStarsEst. cost / yrCompare
Gree GMV-VQ450WM/C-X(A)45 kW heating45 kW cooling22,348 kWh/yr2$7,375
Gree GMV-400WM/C-X(A)40 kW heating40 kW cooling17,377 kWh/yr2.5$5,734

Compare GMV-450WM/C-X(A) with another model

Gree GMV-450WM specifications

Type
Reverse cycle
Configuration
Multi-split / VRF
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
45.00 kW
Cooling power input
12.89 kW
Rated heating capacity (7 Β°C)
45.00 kW
Heating power input
11.60 kW
EER, full load (tested)
3.49
COP, full load (tested)
3.88
Rated AEER
3.42
Rated ACOP
3.80
Standby power (PIA)
76.0 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
Yes
Country of manufacture
China

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Gree GMV-450WM zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––5,8735,621
Coldresidential2.51.52,77717,945
Mixedcommercial––7,3862,867
Mixedresidential2.52.04,3166,389
Hotcommercial––16,353678
Hotresidential3.03.012,2881,026
Part-load test points (20 values)
h__h2_ext_cap_power_rated
15610 W
c__t1_half_cap_power_rated
4550 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
4580 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
35950 W
h__h1_half_cap_heat_cap_rated
22500 W
h__h2_is_capable_extended_load
Yes
c__low_temp_full_cap_power_rated
11781.460000000001 W
c__low_temp_half_cap_power_rated
4158.7 W
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
22500 W
c__low_temp_have_half_cap_results
No
c__low_temp_full_cap_cooling_cap_rated
48465 W
c__low_temp_half_cap_cooling_cap_rated
24232.5 W

New Zealand E3 registration details

Registration number
AAC6834
GEMS registration id
148172
Status
approved, available (self-reported)
Registration expires
21 July 2027
Registered for sale in
Australia, Fiji, New Zealand
Family
–
Regulatory standard
[SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.4:2012
MEPS
2019
Product class
Class 21

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. How the derived figures are calculated.