New Zealand Β· costs in NZD

Reverse cycle multi-split / vrf air conditioner
Hitachi RAS-140HNCELW Heat Pump
Hitachi RAS-140HNCELW is a 40 kW reverse cycle multi-split / vrf heat pump registered for sale in New Zealand under the trans-Tasman E3 energy rating scheme (registration AAC9899).
- Energy rating (cooling)
- 2.5
- Heating: 2
- Annual electricity use
- 18,609 kWh
- 2,584 cooling + 16,025 heating
- Estimated running cost
- $6,141 / year
- $512 / month Β· $61,410 over 10 years
- Capacity
- 40 kW cooling
- 45 kW heating
13% less electricity than the median of 18 comparable 40 kW reverse cycle multi-split / vrf registrations (21,358 kWh a year) in the cold zone. Uses less than 72% of them.
Across all 3,611 air conditioner registrations sold in Australia, it uses less than 7% (this compares very different sizes, so the cohort figure above is the useful one).
Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ 33c/kWh in NZD; change the price above to your tariff.
Hitachi RAS-140HNCELW running cost by climate zone
| Climate zone | kWh / year | Per year | 10 years |
|---|---|---|---|
| Cold zone | 18,609 | $6,141 | $61,410 |
| Mixed zone | 9,658 | $3,187 | $31,871 |
| Hot zone | 12,431 | $4,102 | $41,022 |
At 33c/kWh. Formula: cost = annual kWh Γ price. The kWh figure is the labelβs residential estimate for that zone; commercial-profile figures are in the specifications.
Heat pumps that use less electricity
Same configuration and type, cooling capacity within 12% of 40 kW, at least 3% lower annual kWh in the cold zone.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Toshiba MMY-MUP14S1HT8P-A40 kW heating40 kW cooling2,476 kWh/yr | 2.5 | $817 | |
| Mitsubishi Electric PUHY-M350YXM series40 kW heating40 kW cooling3,340 kWh/yr | 1.5 | $1,102 | |
| Mitsubishi Electric PUHY-M350YXM-A40 kW heating40 kW cooling3,340 kWh/yr | 1.5 | $1,102 | |
| Panasonic U-14MF3R745 kW heating40 kW cooling17,008 kWh/yr | 3 | $5,613 |
Heat pumps similar to the Hitachi RAS-140HNCELW
Technically comparable registrations: same configuration and type, capacity within 12%.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Mitsubishi Heavy Industries FDC400KXZRE240 kW heating40 kW cooling20,055 kWh/yr | 2.5 | $6,618 | |
| Mitsubishi Electric PUHY-M350YXM series40 kW heating40 kW cooling3,340 kWh/yr | 1.5 | $1,102 | |
| Toshiba MMY-MUP14S1HT8P-A40 kW heating40 kW cooling2,476 kWh/yr | 2.5 | $817 | |
| Toshiba MMY-MUP1401FT8P-A40 kW heating40 kW cooling21,195 kWh/yr | 3.5 | $6,994 | |
| Panasonic U-14MF3R745 kW heating40 kW cooling17,008 kWh/yr | 3 | $5,613 | |
| Daikin REYA14AYM45 kW heating40 kW cooling21,929 kWh/yr | 2.5 | $7,237 | |
| Mitsubishi Heavy Industries FDC400KXZE245 kW heating40 kW cooling18,736 kWh/yr | 3 | $6,183 | |
| Mitsubishi Electric PUHY-M350YXM-A-BS40 kW heating40 kW cooling3,340 kWh/yr | 1.5 | $1,102 |
Compare RAS-140HNCELW with another model
Hitachi RAS-140HNCELW specifications
- Type
- Reverse cycle
- Configuration
- Multi-split / VRF
- Air distribution
- Ducted or non-ducted
- Indoor unit
- β
- Rated cooling capacity (35 Β°C)
- 40.00 kW
- Cooling power input
- 12.45 kW
- Rated heating capacity (7 Β°C)
- 45.00 kW
- Heating power input
- 11.15 kW
- EER, full load (tested)
- 3.14
- COP, full load (tested)
- 3.92
- Rated AEER
- 3.16
- Rated ACOP
- 3.96
- Standby power (PIA)
- 66.0 W
- Compressor
- Variable speed, Inverter
- Refrigerant
- R410A
- Power supply
- Three phase
- Indoor sound power
- β
- Outdoor sound power
- β
- Demand response (AS/NZS 4755)
- Yes
- Country of manufacture
- China, Japan
Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.
Hitachi RAS-140HNCELW zoned energy rating figures
As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.
| Zone | Profile | Cooling stars | Heating stars | Cooling kWh | Heating kWh |
|---|---|---|---|---|---|
| Coldcommercial | commercial | β | β | 5,457 | 4,962 |
| Coldresidential | residential | 2.5 | 2.0 | 2,584 | 16,025 |
| Mixedcommercial | commercial | β | β | 6,888 | 2,485 |
| Mixedresidential | residential | 2.5 | 2.5 | 4,042 | 5,616 |
| Hotcommercial | commercial | β | β | 15,336 | 583 |
| Hotresidential | residential | 2.5 | 3.5 | 11,546 | 885 |
Part-load test points (16 values)
- h__h2_ext_cap_power_rated
- 17921 W
- c__t1_half_cap_power_rated
- 4209 W
- c__t1_have_min_cap_results
- No
- h__h1_half_cap_power_rated
- 3925 W
- h__h1_have_min_cap_results
- No
- h__h3_have_ext_cap_results
- No
- h__h2_have_full_cap_results
- No
- h__h2_have_half_cap_results
- No
- h__h3_have_full_cap_results
- No
- h__h3_have_half_cap_results
- No
- h__h2_ext_cap_heat_cap_rated
- 40179 W
- h__h1_half_cap_heat_cap_rated
- 22500 W
- h__h2_is_capable_extended_load
- Yes
- c__low_temp_have_min_cap_results
- No
- c__t1_half_cap_cooling_cap_rated
- 20000 W
- c__low_temp_have_half_cap_results
- No
New Zealand E3 registration details
- Registration number
- AAC9899
- GEMS registration id
- 177202
- Status
- approved, available (self-reported)
- Registration expires
- 21 March 2031
- Registered for sale in
- Australia, New Zealand
- Family
- β
- Regulatory standard
- [SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
- Test standard
- AS/NZS 3823.1.4:2012
- MEPS
- 2019
- Product class
- Class 21
Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: temperzone.com. How the derived figures are calculated.