c/kWh
Energy rating (cooling)
2.5
Heating: 2
Annual electricity use
18,609 kWh
2,584 cooling + 16,025 heating
Estimated running cost
$6,141 / year
$512 / month Β· $61,410 over 10 years
Capacity
40 kW cooling
45 kW heating

13% less electricity than the median of 18 comparable 40 kW reverse cycle multi-split / vrf registrations (21,358 kWh a year) in the cold zone. Uses less than 72% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 7% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Hitachi RAS-140HNCELW running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 18,609$6,141$61,410
Mixed zone 9,658$3,187$31,871
Hot zone 12,431$4,102$41,022

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 40 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
Toshiba MMY-MUP14S1HT8P-A40 kW heating40 kW cooling2,476 kWh/yr2.5$817
Mitsubishi Electric PUHY-M350YXM series40 kW heating40 kW cooling3,340 kWh/yr1.5$1,102
Mitsubishi Electric PUHY-M350YXM-A40 kW heating40 kW cooling3,340 kWh/yr1.5$1,102
Panasonic U-14MF3R745 kW heating40 kW cooling17,008 kWh/yr3$5,613

Heat pumps similar to the Hitachi RAS-140HNCELW

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Mitsubishi Heavy Industries FDC400KXZRE240 kW heating40 kW cooling20,055 kWh/yr2.5$6,618
Mitsubishi Electric PUHY-M350YXM series40 kW heating40 kW cooling3,340 kWh/yr1.5$1,102
Toshiba MMY-MUP14S1HT8P-A40 kW heating40 kW cooling2,476 kWh/yr2.5$817
Toshiba MMY-MUP1401FT8P-A40 kW heating40 kW cooling21,195 kWh/yr3.5$6,994
Panasonic U-14MF3R745 kW heating40 kW cooling17,008 kWh/yr3$5,613
Daikin REYA14AYM45 kW heating40 kW cooling21,929 kWh/yr2.5$7,237
Mitsubishi Heavy Industries FDC400KXZE245 kW heating40 kW cooling18,736 kWh/yr3$6,183
Mitsubishi Electric PUHY-M350YXM-A-BS40 kW heating40 kW cooling3,340 kWh/yr1.5$1,102

Compare RAS-140HNCELW with another model

Hitachi RAS-140HNCELW specifications

Type
Reverse cycle
Configuration
Multi-split / VRF
Air distribution
Ducted or non-ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
40.00 kW
Cooling power input
12.45 kW
Rated heating capacity (7 Β°C)
45.00 kW
Heating power input
11.15 kW
EER, full load (tested)
3.14
COP, full load (tested)
3.92
Rated AEER
3.16
Rated ACOP
3.96
Standby power (PIA)
66.0 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
Yes
Country of manufacture
China, Japan

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Hitachi RAS-140HNCELW zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––5,4574,962
Coldresidential2.52.02,58416,025
Mixedcommercial––6,8882,485
Mixedresidential2.52.54,0425,616
Hotcommercial––15,336583
Hotresidential2.53.511,546885
Part-load test points (16 values)
h__h2_ext_cap_power_rated
17921 W
c__t1_half_cap_power_rated
4209 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
3925 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
40179 W
h__h1_half_cap_heat_cap_rated
22500 W
h__h2_is_capable_extended_load
Yes
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
20000 W
c__low_temp_have_half_cap_results
No

New Zealand E3 registration details

Registration number
AAC9899
GEMS registration id
177202
Status
approved, available (self-reported)
Registration expires
21 March 2031
Registered for sale in
Australia, New Zealand
Family
–
Regulatory standard
[SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.4:2012
MEPS
2019
Product class
Class 21

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: temperzone.com. How the derived figures are calculated.