New Zealand Β· costs in NZD

Reverse cycle split system air conditioner, cassette
Midea MFAB-60WC/MULMIO12 Heat Pump
Midea MFAB-60WC/MULMIO12 is a 3.6 kW reverse cycle split system heat pump registered for sale in New Zealand under the trans-Tasman E3 energy rating scheme (registration AAC8169).
- Energy rating (cooling)
- 4
- Heating: 2.5
- Annual electricity use
- 1,383 kWh
- 167 cooling + 1,216 heating
- Estimated running cost
- $456 / year
- $38 / month Β· $4,564 over 10 years
- Capacity
- 3.6 kW cooling
- 3.9 kW heating
1% less electricity than the median of 187 comparable 3.5 kW reverse cycle split system registrations (1,395 kWh a year) in the cold zone. Uses less than 55% of them.
Across all 3,611 air conditioner registrations sold in Australia, it uses less than 82% (this compares very different sizes, so the cohort figure above is the useful one).
Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ 33c/kWh in NZD; change the price above to your tariff.
Midea MFAB-60WC running cost by climate zone
| Climate zone | kWh / year | Per year | 10 years |
|---|---|---|---|
| Cold zone | 1,383 | $456 | $4,564 |
| Mixed zone | 737 | $243 | $2,432 |
| Hot zone | 834 | $275 | $2,752 |
At 33c/kWh. Formula: cost = annual kWh Γ price. The kWh figure is the labelβs residential estimate for that zone; commercial-profile figures are in the specifications.
Heat pumps that use less electricity
Same configuration and type, cooling capacity within 12% of 3.6 kW, at least 3% lower annual kWh in the cold zone.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Midea MFCA35VA-W/MFCA35VA-N3.6 kW heating3.5 kW cooling1,144 kWh/yr | 5.5 | $378 | |
| Daikin RXM35AVMA / FTXM35AVMA3.7 kW heating3.5 kW cooling1,146 kWh/yr | 5.5 | $378 | |
| Midea MFEP35VA-W/MFEP35VA-N3.6 kW heating3.5 kW cooling1,183 kWh/yr | 6 | $390 | |
| Daikin RXV35AVMA / FTXV35AVMA3.7 kW heating3.5 kW cooling1,207 kWh/yr | 5 | $398 | |
| Hitachi RAC-VJ35PHAT/RAK-VJ35PHAT3.8 kW heating3.5 kW cooling1,209 kWh/yr | 5 | $399 |
Heat pumps similar to the Midea MFAB-60WC
Technically comparable registrations: same configuration and type, capacity within 12%.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Toshiba RAV-GM401ATP-A/RAV-HM401MUTP-E4 kW heating3.6 kW cooling1,689 kWh/yr | 2.5 | $557 | |
| Panasonic U-36PZ3R5/S-36PY3E3.6 kW heating3.6 kW cooling1,506 kWh/yr | 2 | $497 | |
| Toshiba RAV-GM401ATP-A/RAV-GM401KRTP-A4 kW heating3.6 kW cooling1,883 kWh/yr | 3 | $621 | |
| Westinghouse WSD36HWA-E/WSD36HWA-I4.4 kW heating3.6 kW cooling1,411 kWh/yr | 5.5 | $466 | |
| Spt AW036C-1/AW036E3.9 kW heating3.6 kW cooling1,246 kWh/yr | 5.5 | $411 | |
| Westinghouse HSV127HWAE/HSV127HWAI4.4 kW heating3.6 kW cooling1,411 kWh/yr | 5.5 | $466 | |
| Aux ASW-H36A4/CAR3DI3.8 kW heating3.5 kW cooling1,303 kWh/yr | 5.5 | $430 | |
| Kaden KSI124 kW heating3.5 kW cooling1,456 kWh/yr | 5 | $480 |
Compare MFAB-60WC/MULMIO12 with another model
Midea MFAB-60WC specifications
- Type
- Reverse cycle
- Configuration
- Split system
- Air distribution
- Non-ducted
- Indoor unit
- Cassette
- Rated cooling capacity (35 Β°C)
- 3.60 kW
- Cooling power input
- 0.97 kW
- Rated heating capacity (7 Β°C)
- 3.90 kW
- Heating power input
- 0.86 kW
- EER, full load (tested)
- 4.01
- COP, full load (tested)
- 4.47
- Rated AEER
- 3.68
- Rated ACOP
- 4.47
- Standby power (PIA)
- 3.2 W
- Compressor
- Variable speed, Inverter
- Refrigerant
- R32
- Power supply
- Single phase
- Indoor sound power
- 60.6 dB(A)
- Outdoor sound power
- 66.3 dB(A)
- Demand response (AS/NZS 4755)
- β
- Country of manufacture
- China
Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.
Midea MFAB-60WC zoned energy rating figures
As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.
| Zone | Profile | Cooling stars | Heating stars | Cooling kWh | Heating kWh |
|---|---|---|---|---|---|
| Coldcommercial | commercial | β | β | 144 | 397 |
| Coldresidential | residential | 4.0 | 2.5 | 167 | 1,216 |
| Mixedcommercial | commercial | β | β | 301 | 214 |
| Mixedresidential | residential | 4.0 | 3.0 | 265 | 472 |
| Hotcommercial | commercial | β | β | 847 | 48 |
| Hotresidential | residential | 4.5 | 3.0 | 760 | 74 |
Part-load test points (25 values)
- c__t1_min_cap_power_rated
- 330 W
- h__h1_min_cap_power_rated
- 237 W
- h__h2_ext_cap_power_rated
- 1355 W
- c__t1_half_cap_power_rated
- 416 W
- c__t1_have_min_cap_results
- Yes
- h__h1_half_cap_power_rated
- 360 W
- h__h1_have_min_cap_results
- Yes
- h__h3_have_ext_cap_results
- No
- h__h2_have_full_cap_results
- No
- h__h2_have_half_cap_results
- No
- h__h3_have_full_cap_results
- No
- h__h3_have_half_cap_results
- No
- h__h1_min_cap_heat_cap_rated
- 1200 W
- h__h2_ext_cap_heat_cap_rated
- 4210 W
- h__h1_half_cap_heat_cap_rated
- 1850 W
- h__h2_is_capable_extended_load
- Yes
- c__low_temp_min_cap_power_rated
- 190 W
- c__t1_min_cap_cooling_cap_rated
- 1150 W
- c__low_temp_full_cap_power_rated
- 884.7520000000001 W
- c__low_temp_half_cap_power_rated
- 300 W
- c__t1_half_cap_cooling_cap_rated
- 1979 W
- c__low_temp_have_half_cap_results
- Yes
- c__low_temp_min_cap_cooling_cap_rated
- 1200 W
- c__low_temp_full_cap_cooling_cap_rated
- 3877.2 W
- c__low_temp_half_cap_cooling_cap_rated
- 2100 W
New Zealand E3 registration details
- Registration number
- AAC8169
- GEMS registration id
- 160627
- Status
- approved, available (self-reported)
- Registration expires
- 9 April 2029
- Registered for sale in
- Australia, Fiji, New Zealand
- Family
- β
- Regulatory standard
- [SEER Non Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
- Test standard
- AS/NZS 3823.1.1:2012
- MEPS
- 2019
- Product class
- Class 8
Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. How the derived figures are calculated.