c/kWh
Energy rating (cooling)
3
Heating: 1.5
Annual electricity use
29,720 kWh
3,856 cooling + 25,864 heating
Estimated running cost
$9,808 / year
$817 / month Β· $98,076 over 10 years
Capacity
65.1 kW cooling
64.5 kW heating

16% less electricity than the median of 16 comparable 65 kW reverse cycle ducted packaged registrations (35,446 kWh a year) in the cold zone. Uses less than 63% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 4% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Temperzone OPA 680RLTB2FPDQ running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 29,720$9,808$98,076
Mixed zone 16,073$5,304$53,041
Hot zone 19,023$6,278$62,776

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 65.1 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
APAC P065AHR3SA-LTT62.9 kW heating63.5 kW cooling4,970 kWh/yr1.5$1,640
APAC P065AHR3SA-RTR62.9 kW heating63.5 kW cooling4,970 kWh/yr1.5$1,640
Temperzone OPA705RKTBG-P67.5 kW heating67.9 kW cooling5,690 kWh/yr1.5$1,878
Temperzone OPA705RKTB66.4 kW heating66 kW cooling5,690 kWh/yr1.5$1,878
Actron Air PKY620T62.5 kW heating60.8 kW cooling5,989 kWh/yr1$1,976

Heat pumps similar to the Temperzone OPA 680RLTB2FPDQ

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Daikin UAYN640AFY1A64.9 kW heating66.2 kW cooling39,023 kWh/yr1.5$12,878
Daikin UAYQ210CY1A64 kW heating63.7 kW cooling36,496 kWh/yr1.5$12,044
APAC P065AHR3SA-LTT62.9 kW heating63.5 kW cooling4,970 kWh/yr1.5$1,640
APAC P065AHR3SA-RTR62.9 kW heating63.5 kW cooling4,970 kWh/yr1.5$1,640
AIRSTAGE RAQ/K/WP/* 23071.6 kW heating68.8 kW cooling43,051 kWh/yr1$14,207
AIRSTAGE RAQ/K/WP/ECO/23071.6 kW heating68.8 kW cooling43,051 kWh/yr1$14,207

Other Temperzone models of similar capacity

ModelStarsEst. cost / yrCompare
Temperzone OPA 680RLTB1FPQ63.5 kW heating65 kW cooling28,933 kWh/yr2$9,548
Temperzone OPA705RKTB66.4 kW heating66 kW cooling5,690 kWh/yr1.5$1,878

Compare OPA 680RLTB2FPDQ with another model

Temperzone OPA 680RLTB2FPDQ specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
65.09 kW
Cooling power input
17.09 kW
Rated heating capacity (7 Β°C)
64.50 kW
Heating power input
16.51 kW
EER, full load (tested)
3.81
COP, full load (tested)
3.91
Rated AEER
3.78
Rated ACOP
3.88
Standby power (PIA)
39.0 W
Compressor
Variable speed, Inverter
Refrigerant
R32
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Australia, New Zealand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Temperzone OPA 680RLTB2FPDQ zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––7,7668,547
Coldresidential3.01.53,85625,864
Mixedcommercial––10,1614,585
Mixedresidential3.02.05,96510,108
Hotcommercial––22,897994
Hotresidential3.02.017,4611,562
Part-load test points (18 values)
h__h2_ext_cap_power_rated
20670 W
c__t1_half_cap_power_rated
7960 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
7670 W
h__h1_have_min_cap_results
No
h__h2_half_cap_power_rated
8580 W
h__h2_have_half_cap_results
Yes
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
59827 W
h__h1_half_cap_heat_cap_rated
30730 W
h__h2_half_cap_heat_cap_rated
26890 W
h__h2_is_capable_extended_load
Yes
c__low_temp_half_cap_power_rated
6380 W
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
33690 W
c__low_temp_have_half_cap_results
Yes
c__low_temp_half_cap_cooling_cap_rated
33850 W

New Zealand E3 registration details

Registration number
AAC8642
GEMS registration id
167485
Status
approved, available (self-reported)
Registration expires
11 March 2030
Registered for sale in
Australia, Fiji, New Zealand
Family
–
Regulatory standard
[SEER Non Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
Test standard
AS/NZS 3823.1.2:2012
MEPS
2020
Product class
Class 24

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. How the derived figures are calculated.