c/kWh
Energy rating (cooling)
2.5
Heating: 0
Annual electricity use
17,446 kWh
3,857 cooling + 13,589 heating
Estimated running cost
$5,583 / year
$465 / month Β· $55,827 over 10 years
Capacity
40 kW cooling
45 kW heating

65% more electricity than the median of 18 comparable 40 kW reverse cycle multi-split / vrf registrations (10,587 kWh a year) in the mixed zone. Uses less than 11% of them.

Across all 3,680 air conditioner registrations sold in Australia, it uses less than 3% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the mixed zone (Richmond NSW climate: Sydney, Melbourne, Adelaide, Perth). Mixed climate zone shown by default (Sydney, Melbourne, Adelaide, Perth); switch to cold or hot. Cost = kWh Γ— 32c/kWh in AUD; change the price above to your tariff.

Mitsubishi Electric PUHY-P350YNW-A1 Series running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 38,458$12,307$123,066
Mixed zone 17,446$5,583$55,827
Hot zone 12,201$3,904$39,043

At 32c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Air conditioners that use less electricity

Same configuration and type, cooling capacity within 12% of 40 kW, at least 3% lower annual kWh in the mixed zone.

ModelStarsEst. cost / yrCompare
Toshiba MMY-MUP14S1HT8P-A40 kW heating40 kW cooling3,918 kWh/yr2.5$1,254
Mitsubishi Electric PUHY-M350YXM-A-BS40 kW heating40 kW cooling5,003 kWh/yr1.5$1,601
Mitsubishi Electric PUHY-M350YXM-A40 kW heating40 kW cooling5,003 kWh/yr1.5$1,601
Panasonic U-14MF3R745 kW heating40 kW cooling8,732 kWh/yr3$2,794
Mitsubishi Heavy Industries FDC400KXZE245 kW heating40 kW cooling9,498 kWh/yr2.5$3,039

Air conditioners similar to the Mitsubishi Electric PUHY-P350YNW-A1 Series

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Toshiba MMY-MUP1401FT8P-A40 kW heating40 kW cooling10,278 kWh/yr3.5$3,289
Hitachi RAS-140RNCBLW45 kW heating40 kW cooling10,547 kWh/yr2$3,375
Daikin REYA14AYM45 kW heating40 kW cooling10,627 kWh/yr2.5$3,401
Mitsubishi Heavy Industries FDC400KXZE245 kW heating40 kW cooling9,498 kWh/yr2.5$3,039
Mitsubishi Heavy Industries FDC400KXZRE240 kW heating40 kW cooling10,236 kWh/yr2.5$3,276
Hitachi RAS-140HNCELW45 kW heating40 kW cooling9,658 kWh/yr2.5$3,091
Toshiba MMY-MUP14S1HT8P-A40 kW heating40 kW cooling3,918 kWh/yr2.5$1,254
Panasonic U-14MF3R745 kW heating40 kW cooling8,732 kWh/yr3$2,794

Compare PUHY-P350YNW-A1 Series with another model

Mitsubishi Electric PUHY-P350YNW-A1 Series specifications

Type
Reverse cycle
Configuration
Multi-split / VRF
Air distribution
Ducted or non-ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
40.00 kW
Cooling power input
11.22 kW
Rated heating capacity (7 Β°C)
45.00 kW
Heating power input
10.94 kW
EER, full load (tested)
3.57
COP, full load (tested)
4.28
Rated AEER
3.49
Rated ACOP
4.02
Standby power (PIA)
76.0 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Thailand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Mitsubishi Electric PUHY-P350YNW-A1 Series zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––4,7429,510
Coldresidential2.50.02,50835,950
Mixedcommercial––6,2284,633
Mixedresidential2.50.03,85713,589
Hotcommercial––14,050801
Hotresidential3.01.510,8901,311
Part-load test points (18 values)
h__h2_ext_cap_power_rated
9870 W
c__t1_half_cap_power_rated
4520 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
4770 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
17800 W
h__h1_half_cap_heat_cap_rated
22500 W
h__h2_is_capable_extended_load
Yes
c__low_temp_half_cap_power_rated
3590 W
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
20000 W
c__low_temp_have_half_cap_results
Yes
c__low_temp_half_cap_cooling_cap_rated
20000 W

Other model numbers on registration AAC9262

Registered together and sharing the same test results. Usually variants of the same unit.

Australian GEMS registration details

Registration number
AAC9262
GEMS registration id
171911
Status
approved, available (self-reported)
Registration expires
20 August 2030
Registered for sale in
Australia, New Zealand
Family
PUHY-P350YNW-A1 Series
Regulatory standard
[SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.4:2012
MEPS
2019
Product class
Class 21

Source: Australian Government Energy Rating (GEMS) registration data, DCCEEW via data.gov.au (CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: MitsubishiElectric.com.au. How the derived figures are calculated.