c/kWh
Energy rating (cooling)
2.5
Heating: 0.5
Annual electricity use
69,163 kWh
6,321 cooling + 62,842 heating
Estimated running cost
$22,824 / year
$1,902 / month Β· $228,238 over 10 years
Capacity
96 kW cooling
97 kW heating

382% more electricity than the median of 14 comparable 80 kW and above reverse cycle ducted split system registrations (14,339 kWh a year) in the cold zone. Uses less than 0% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 0% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Actron Air CRV960T running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 69,163$22,824$228,238
Mixed zone 33,378$11,015$110,147
Hot zone 30,668$10,120$101,204

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 96 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
Temperzone OSA950RKTBGV/ISD950KBXH-P90.4 kW heating88.7 kW cooling8,257 kWh/yr1$2,725
APAC S095OVR3SA- / S095IHR3SA--FR92.2 kW heating94.1 kW cooling8,763 kWh/yr1$2,892
APAC S095OVR3SA- / S095IHR3SA--TR92.2 kW heating94.1 kW cooling8,763 kWh/yr1$2,892
Actron Air CRV85AT / EVA85AT86 kW heating85 kW cooling43,088 kWh/yr2.5$14,219
Actron Air CRV850T / EVA850T86 kW heating85 kW cooling50,142 kWh/yr2.5$16,547

Heat pumps similar to the Actron Air CRV960T

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
APAC S095OVR3SA- / S095IHR3SA--FR92.2 kW heating94.1 kW cooling8,763 kWh/yr1$2,892
APAC S095OVR3SA- / S095IHR3SA--TR92.2 kW heating94.1 kW cooling8,763 kWh/yr1$2,892
Temperzone OSA950RKTBGV/ISD950KBXH-P90.4 kW heating88.7 kW cooling8,257 kWh/yr1$2,725

Other Actron Air models of similar capacity

ModelStarsEst. cost / yrCompare
Actron Air CRV96AT / EVA96AT97 kW heating96 kW cooling54,965 kWh/yr2.5$18,138
Actron Air CRV85AT / EVA85AT86 kW heating85 kW cooling43,088 kWh/yr2.5$14,219

Compare CRV960T / EVA960T with another model

Actron Air CRV960T specifications

Type
Reverse cycle
Configuration
Split system
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
96.00 kW
Cooling power input
27.92 kW
Rated heating capacity (7 Β°C)
97.00 kW
Heating power input
25.84 kW
EER, full load (tested)
3.35
COP, full load (tested)
3.66
Rated AEER
3.38
Rated ACOP
3.69
Standby power (PIA)
138.4 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
Yes
Country of manufacture
Australia

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Actron Air CRV960T zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––13,68617,909
Coldresidential2.50.56,32162,842
Mixedcommercial––17,1299,027
Mixedresidential2.00.59,77223,606
Hotcommercial––37,6941,657
Hotresidential2.52.028,1032,565
Part-load test points (16 values)
h__h2_ext_cap_power_rated
21779 W
c__t1_half_cap_power_rated
10838 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
11328 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
50400 W
h__h1_half_cap_heat_cap_rated
48100 W
h__h2_is_capable_extended_load
Yes
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
47830 W
c__low_temp_have_half_cap_results
No

New Zealand E3 registration details

Registration number
AAC7072
GEMS registration id
141941
Status
approved, available (self-reported)
Registration expires
4 October 2027
Registered for sale in
Australia, New Zealand
Family
–
Regulatory standard
[SEER Non Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
Test standard
AS/NZS 3823.1.2:2012
MEPS
2020
Product class
Class 25

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: actronair.com.au. How the derived figures are calculated.