New Zealand Β· costs in NZD

Reverse cycle split system air conditioner
Actron Air CRV96AT / EVA96AT Heat Pump
Actron Air CRV96AT / EVA96AT is a 96 kW reverse cycle ducted split system heat pump registered for sale in New Zealand under the trans-Tasman E3 energy rating scheme (registration AAC8586).
- Energy rating (cooling)
- 2.5
- Heating: 1
- Annual electricity use
- 54,965 kWh
- 6,256 cooling + 48,709 heating
- Estimated running cost
- $18,138 / year
- $1,512 / month Β· $181,385 over 10 years
- Capacity
- 96 kW cooling
- 97 kW heating
283% more electricity than the median of 14 comparable 80 kW and above reverse cycle ducted split system registrations (14,339 kWh a year) in the cold zone. Uses less than 7% of them.
Across all 3,611 air conditioner registrations sold in Australia, it uses less than 1% (this compares very different sizes, so the cohort figure above is the useful one).
Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ 33c/kWh in NZD; change the price above to your tariff.
Actron Air CRV96AT running cost by climate zone
| Climate zone | kWh / year | Per year | 10 years |
|---|---|---|---|
| Cold zone | 54,965 | $18,138 | $181,385 |
| Mixed zone | 26,870 | $8,867 | $88,671 |
| Hot zone | 29,608 | $9,771 | $97,706 |
At 33c/kWh. Formula: cost = annual kWh Γ price. The kWh figure is the labelβs residential estimate for that zone; commercial-profile figures are in the specifications.
Heat pumps that use less electricity
Same configuration and type, cooling capacity within 12% of 96 kW, at least 3% lower annual kWh in the cold zone.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Temperzone OSA950RKTBGV/ISD950KBXH-P90.4 kW heating88.7 kW cooling8,257 kWh/yr | 1 | $2,725 | |
| APAC S095OVR3SA- / S095IHR3SA--FR92.2 kW heating94.1 kW cooling8,763 kWh/yr | 1 | $2,892 | |
| APAC S095OVR3SA- / S095IHR3SA--TR92.2 kW heating94.1 kW cooling8,763 kWh/yr | 1 | $2,892 | |
| Actron Air CRV85AT / EVA85AT86 kW heating85 kW cooling43,088 kWh/yr | 2.5 | $14,219 | |
| Actron Air CRV850T / EVA850T86 kW heating85 kW cooling50,142 kWh/yr | 2.5 | $16,547 |
Heat pumps similar to the Actron Air CRV96AT
Technically comparable registrations: same configuration and type, capacity within 12%.
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| APAC S095OVR3SA- / S095IHR3SA--FR92.2 kW heating94.1 kW cooling8,763 kWh/yr | 1 | $2,892 | |
| APAC S095OVR3SA- / S095IHR3SA--TR92.2 kW heating94.1 kW cooling8,763 kWh/yr | 1 | $2,892 | |
| Temperzone OSA950RKTBGV/ISD950KBXH-P90.4 kW heating88.7 kW cooling8,257 kWh/yr | 1 | $2,725 |
Other Actron Air models of similar capacity
| Model | Stars | Est. cost / yr | Compare |
|---|---|---|---|
| Actron Air CRV960T / EVA960T97 kW heating96 kW cooling69,163 kWh/yr | 2.5 | $22,824 | |
| Actron Air CRV85AT / EVA85AT86 kW heating85 kW cooling43,088 kWh/yr | 2.5 | $14,219 |
Compare CRV96AT / EVA96AT with another model
Actron Air CRV96AT specifications
- Type
- Reverse cycle
- Configuration
- Split system
- Air distribution
- Ducted
- Indoor unit
- β
- Rated cooling capacity (35 Β°C)
- 96.00 kW
- Cooling power input
- 27.25 kW
- Rated heating capacity (7 Β°C)
- 97.00 kW
- Heating power input
- 24.23 kW
- EER, full load (tested)
- 3.44
- COP, full load (tested)
- 3.93
- Rated AEER
- 3.46
- Rated ACOP
- 3.92
- Standby power (PIA)
- 150.0 W
- Compressor
- Variable speed, Inverter
- Refrigerant
- R32
- Power supply
- Three phase
- Indoor sound power
- β
- Outdoor sound power
- β
- Demand response (AS/NZS 4755)
- Yes
- Country of manufacture
- Australia
Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.
Actron Air CRV96AT zoned energy rating figures
As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.
| Zone | Profile | Cooling stars | Heating stars | Cooling kWh | Heating kWh |
|---|---|---|---|---|---|
| Coldcommercial | commercial | β | β | 12,129 | 14,355 |
| Coldresidential | residential | 2.5 | 1.0 | 6,256 | 48,709 |
| Mixedcommercial | commercial | β | β | 15,863 | 6,954 |
| Mixedresidential | residential | 2.5 | 1.5 | 9,605 | 17,265 |
| Hotcommercial | commercial | β | β | 35,641 | 1,419 |
| Hotresidential | residential | 3.0 | 3.0 | 27,429 | 2,179 |
Part-load test points (18 values)
- h__h2_ext_cap_power_rated
- 22030 W
- c__t1_half_cap_power_rated
- 11700 W
- c__t1_have_min_cap_results
- No
- h__h1_half_cap_power_rated
- 9570 W
- h__h1_have_min_cap_results
- No
- h__h3_have_ext_cap_results
- No
- h__h2_have_full_cap_results
- No
- h__h2_have_half_cap_results
- No
- h__h3_have_full_cap_results
- No
- h__h3_have_half_cap_results
- No
- h__h2_ext_cap_heat_cap_rated
- 60400 W
- h__h1_half_cap_heat_cap_rated
- 47460 W
- h__h2_is_capable_extended_load
- Yes
- c__low_temp_half_cap_power_rated
- 9360 W
- c__low_temp_have_min_cap_results
- No
- c__t1_half_cap_cooling_cap_rated
- 47530 W
- c__low_temp_have_half_cap_results
- Yes
- c__low_temp_half_cap_cooling_cap_rated
- 47920 W
New Zealand E3 registration details
- Registration number
- AAC8586
- GEMS registration id
- 166761
- Status
- approved, available (self-reported)
- Registration expires
- 22 January 2030
- Registered for sale in
- Australia, New Zealand
- Family
- β
- Regulatory standard
- [SEER Non Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
- Test standard
- AS/NZS 3823.1.2:2012
- MEPS
- 2020
- Product class
- Class 25
Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: actronair.com.au. How the derived figures are calculated.