c/kWh
Energy rating (cooling)
2.5
Heating: 0
Annual electricity use
39,130 kWh
2,461 cooling + 36,669 heating
Estimated running cost
$12,913 / year
$1,076 / month Β· $129,129 over 10 years
Capacity
40 kW cooling
45 kW heating

83% more electricity than the median of 18 comparable 40 kW reverse cycle multi-split / vrf registrations (21,358 kWh a year) in the cold zone. Uses less than 6% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 2% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Mitsubishi Electric PURY-EP350YNW-A1 Series running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 39,130$12,913$129,129
Mixed zone 17,766$5,863$58,628
Hot zone 11,992$3,957$39,574

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 40 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
Toshiba MMY-MUP14S1HT8P-A40 kW heating40 kW cooling2,476 kWh/yr2.5$817
Mitsubishi Electric PUHY-M350YXM-A40 kW heating40 kW cooling3,340 kWh/yr1.5$1,102
Mitsubishi Electric PUHY-M350YXM-A-BS40 kW heating40 kW cooling3,340 kWh/yr1.5$1,102
Panasonic U-14MF3R745 kW heating40 kW cooling17,008 kWh/yr3$5,613
Hitachi RAS-140HNCELW45 kW heating40 kW cooling18,609 kWh/yr2.5$6,141

Heat pumps similar to the Mitsubishi Electric PURY-EP350YNW-A1 Series

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Panasonic U-14MF3R745 kW heating40 kW cooling17,008 kWh/yr3$5,613
Hitachi RAS-140RNCBLW45 kW heating40 kW cooling20,084 kWh/yr1.5$6,628
Toshiba MMY-MUP1401FT8P-A40 kW heating40 kW cooling21,195 kWh/yr3.5$6,994
Daikin REYA14AYM45 kW heating40 kW cooling21,929 kWh/yr2.5$7,237
Mitsubishi Heavy Industries FDC400KXZE245 kW heating40 kW cooling18,736 kWh/yr3$6,183
Mitsubishi Heavy Industries FDC400KXZRE240 kW heating40 kW cooling20,055 kWh/yr2.5$6,618
Hitachi RAS-140HNCELW45 kW heating40 kW cooling18,609 kWh/yr2.5$6,141
Toshiba MMY-MUP14S1HT8P-A40 kW heating40 kW cooling2,476 kWh/yr2.5$817

Compare PURY-EP350YNW-A1 Series with another model

Mitsubishi Electric PURY-EP350YNW-A1 Series specifications

Type
Reverse cycle
Configuration
Multi-split / VRF
Air distribution
Ducted or non-ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
40.00 kW
Cooling power input
10.75 kW
Rated heating capacity (7 Β°C)
45.00 kW
Heating power input
11.84 kW
EER, full load (tested)
3.85
COP, full load (tested)
3.95
Rated AEER
3.63
Rated ACOP
3.72
Standby power (PIA)
80.7 W
Compressor
Variable speed, Inverter
Refrigerant
R410A
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Thailand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Mitsubishi Electric PURY-EP350YNW-A1 Series zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––4,6189,875
Coldresidential2.50.02,46136,669
Mixedcommercial––6,0664,869
Mixedresidential2.50.03,76913,997
Hotcommercial––13,635865
Hotresidential3.01.510,5841,408
Part-load test points (18 values)
h__h2_ext_cap_power_rated
9880 W
c__t1_half_cap_power_rated
4450 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
5270 W
h__h1_have_min_cap_results
No
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
No
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
18100 W
h__h1_half_cap_heat_cap_rated
22500 W
h__h2_is_capable_extended_load
Yes
c__low_temp_half_cap_power_rated
3520 W
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
20000 W
c__low_temp_have_half_cap_results
Yes
c__low_temp_half_cap_cooling_cap_rated
20000 W

Other model numbers on registration AAC9241

Registered together and sharing the same test results. Usually variants of the same unit.

New Zealand E3 registration details

Registration number
AAC9241
GEMS registration id
172055
Status
approved, available (self-reported)
Registration expires
19 August 2030
Registered for sale in
Australia, New Zealand
Family
PURY-EP350YNW-A1 Series
Regulatory standard
[SEER Multi-Split <=65kW] GEMS (Air Conditioners up to 65kW) Determination 2019
Test standard
AS/NZS 3823.1.4:2012
MEPS
2019
Product class
Class 21

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 25 September 2026; last checked 26 September 2026. Manufacturer: MitsubishiElectric.com.au. How the derived figures are calculated.