c/kWh
Energy rating (cooling)
1.5
Heating: 1
Annual electricity use
75,013 kWh
12,421 cooling + 62,592 heating
Estimated running cost
$24,754 / year
$2,063 / month Β· $247,543 over 10 years
Capacity
140.2 kW cooling
142.1 kW heating

81% more electricity than the median of 53 comparable 80 kW and above reverse cycle ducted packaged registrations (41,538 kWh a year) in the cold zone. Uses less than 17% of them.

Across all 3,611 air conditioner registrations sold in Australia, it uses less than 0% (this compares very different sizes, so the cohort figure above is the useful one).

coolingheatingClick a zone to use it across the page.

Annual kWh is the government label figure for a residential user in the cold zone (Canberra climate: Canberra, Hobart, Ballarat, alpine areas). All of New Zealand is the cold zone on the Zoned Energy Rating Label. Cost = kWh Γ— 33c/kWh in NZD; change the price above to your tariff.

Temperzone OPA 1410RLTM1FPQ running cost by climate zone

Climate zonekWh / yearPer year10 years
Cold zone 75,013$24,754$247,543
Mixed zone 44,379$14,645$146,451
Hot zone 60,181$19,860$198,597

At 33c/kWh. Formula: cost = annual kWh Γ— price. The kWh figure is the label’s residential estimate for that zone; commercial-profile figures are in the specifications.

Heat pumps that use less electricity

Same configuration and type, cooling capacity within 12% of 140.2 kW, at least 3% lower annual kWh in the cold zone.

ModelStarsEst. cost / yrCompare
Temperzone OPA1400RKTMDF-P115.1 kW heating127.6 kW cooling9,419 kWh/yr2$3,108
Caa HPC125R3AD138.3 kW heating127.5 kW cooling11,262 kWh/yr1.5$3,716
Temperzone OPA1370RKTMG-P125.5 kW heating131.6 kW cooling11,398 kWh/yr1.5$3,761
Daikin UAXYA130NY1130 kW heating130 kW cooling12,660 kWh/yr1$4,178
Daikin UAXYA130SY1130 kW heating130 kW cooling12,660 kWh/yr1$4,178

Heat pumps similar to the Temperzone OPA 1410RLTM1FPQ

Technically comparable registrations: same configuration and type, capacity within 12%.

ModelStarsEst. cost / yrCompare
Actron Air PKV1400T134 kW heating135 kW cooling12,716 kWh/yr1$4,196
Daikin UAXYA130SY1130 kW heating130 kW cooling12,660 kWh/yr1$4,178
Daikin UAXYA130NY1130 kW heating130 kW cooling12,660 kWh/yr1$4,178
Caa HPC125R3AD138.3 kW heating127.5 kW cooling11,262 kWh/yr1.5$3,716
AIRSTAGE URT-EC-WP-MS-111-SK136 kW heating127 kW cooling70,494 kWh/yr1.5$23,263
AIRSTAGE URT/EC/WP/MS/111/SK136 kW heating127 kW cooling70,494 kWh/yr1.5$23,263

Other Temperzone models of similar capacity

ModelStarsEst. cost / yrCompare
Temperzone OPA1370RLTMFQ-P130.9 kW heating136.7 kW cooling12,152 kWh/yr1.5$4,010
Temperzone OPA 1410RLTM4FDPQ148.6 kW heating146 kW cooling66,432 kWh/yr2$21,923

Compare OPA 1410RLTM1FPQ with another model

Temperzone OPA 1410RLTM1FPQ specifications

Type
Reverse cycle
Configuration
Packaged
Air distribution
Ducted
Indoor unit
–
Rated cooling capacity (35 Β°C)
140.20 kW
Cooling power input
45.98 kW
Rated heating capacity (7 Β°C)
142.14 kW
Heating power input
39.58 kW
EER, full load (tested)
3.05
COP, full load (tested)
3.59
Rated AEER
3.04
Rated ACOP
3.58
Standby power (PIA)
41.5 W
Compressor
Variable speed, Single Variable speed system + 3 fixed compressors that turn ON/OFF appropriately
Refrigerant
R32
Power supply
Three phase
Indoor sound power
–
Outdoor sound power
–
Demand response (AS/NZS 4755)
No
Country of manufacture
Australia, New Zealand

Dimensions are not collected for registrations under the 2019 Determination, so they are shown only where the source has them.

Temperzone OPA 1410RLTM1FPQ zoned energy rating figures

As published for each climate zone. Residential figures drive the star ratings; commercial figures assume a commercial usage pattern.

ZoneCooling starsHeating starsCooling kWhHeating kWh
Coldcommercial––29,18321,744
Coldresidential1.51.012,42162,592
Mixedcommercial––36,05612,140
Mixedresidential1.51.518,92125,458
Hotcommercial––77,1512,623
Hotresidential1.51.056,0644,117
Part-load test points (18 values)
h__h2_ext_cap_power_rated
39000 W
c__t1_half_cap_power_rated
25446 W
c__t1_have_min_cap_results
No
h__h1_half_cap_power_rated
22455 W
h__h1_have_min_cap_results
No
h__h2_half_cap_power_rated
21300 W
h__h3_have_ext_cap_results
No
h__h2_have_full_cap_results
No
h__h2_have_half_cap_results
Yes
h__h3_have_full_cap_results
No
h__h3_have_half_cap_results
No
h__h2_ext_cap_heat_cap_rated
129857 W
h__h1_half_cap_heat_cap_rated
71330 W
h__h2_half_cap_heat_cap_rated
62874 W
h__h2_is_capable_extended_load
Yes
c__low_temp_have_min_cap_results
No
c__t1_half_cap_cooling_cap_rated
70825 W
c__low_temp_have_half_cap_results
No

New Zealand E3 registration details

Registration number
AAC8134
GEMS registration id
160026
Status
approved, available (self-reported)
Registration expires
24 March 2029
Registered for sale in
Australia, Fiji, New Zealand
Family
–
Regulatory standard
[SEER Non Multi-Split >65kW] GEMS (Air Conditioners above 65kW) Determination 2022
Test standard
AS/NZS 3823.1.2:2012
MEPS
2020
Product class
Class 24

Source: E3 programme registration data (EECA, New Zealand) (trans-Tasman E3 registration data published by DCCEEW on data.gov.au, CC BY 3.0 AU). Dataset published 19 September 2026; last checked 20 September 2026. How the derived figures are calculated.